nitrogen blanket HVS' patented second generation nitrogen generator system was designed for use on transformer main tanks, tap changers, breakers and any other electrical device requiring a nitrogen gas-blanketed enclosure. This robust system offers a controlled environment to ensure consistent nitrogen purity and supplies compressed nitrogen gas at a much lower psi than traditional bottle pressures to significantly reduce the possibility of system leaks.2nd Generation N2 Generator System

Other benefits include the following:
    • Eliminates the need to lift and risks of replacing
      nitrogen bottles
    • Four non-powered alarm contacts monitor
      condition of the nitrogen generator system
      externally
    • Industry standard lockable cabinet fits same
      footprint as fully-enclosed inert air system, and
      nitrogen gas line exiting the enclosure is in a
      standard location to make installation easy,
      especially in retrofit applications
    • Positive pressure nitrogen gas regulation system
      maintains transformer tank pressure between
      0.2 and 5.5 psi to protect transformer oil from
      oxidation and moisture absorption

High purity nitrogen gas is generated as needed and stored in a tank to provide a reserve supply of nitrogen in the event of power failure. Included SCADA output terminals monitor low/high transformer pressure, low storage tank pressure and control system temperature alarm. A coalescing filter assembly protects hollow fiber nitrogen membrane from particle contamination, while a climate control module regulates system temperature for optimum nitrogen purity (99% to 99.5%).

For more performance and electrical / mechanical specifications as well as return on investment information on our second generation nitrogen generator systems, please contact us at the phone/e-mail address above or download the following brochure (in Adobe Acrobat format):

   2nd Generation Nitrogen Generator Brochure (2Mb)
 
 
About HVS Capabilities Certifications Markets Served Directions to HVS
Oil Circuit Breaker Kits Load Tap Changer Expertise Flexible Lease Kits Transformer Health Products
GE Breaker Components
Reverse Engineering Load Tap Changer Failure Analysis Design Enhancements LTC Training
Instruction Manuals Product Service Advisories Waukesha Service Ask The Expert